PACIFIC PC3250 100M
CABLE TPS 2CE 2.5mm WH RD/BK
Reviews
Specifications
Technical Report of 2.5sqmm Cu/PVC/PVC 2C + E TPS Cable
Type: PVC-Insulated, PVC Sheathed 450/750V Electric Cable
Cross-sectional area: 2 X 2.5 mm2
Conductor Construction: 7/0.67 mm
Cross-sectional area (Earth): 2.5 mm2
Conductor Construction: 7/0.67 mm
Conductor Material: Circular, Stranded, Plain, Annealed Copper (Class 2)
Insulation Material: V-90
Color of Insulation: Red, Black, Green & Yellow
Sheath Material: 3V-90
Color of Sheath: White
Reference Standards: AS/NZS 5000.2
AS/NZS 1125
AS/NZS 1660
Conductor | |||
Test Parameter | Unit | Specified Value | |
Nominal Diameter | Main | mm | 1.98 |
Earth | 1.98 | ||
Maximum Reistance at 20°C | Main | Ω/km | 7.41 |
Earth | 7.41 | ||
Minimum Anealing of Wire | Main | % | 18 |
Earth | 18 | ||
Insulation | |||
Test Parameter | Unit | Specified Value | |
Nominal Thickness | Main | mm | 0.7 |
Earth | 0.7 | ||
Minimum Thickness | Main | mm | 0.53 |
Earth | 0.53 | ||
Tensile Strength (Before Ageing) | Min | N/mm2 | 12.5 |
Elongation (Before Ageing) | Min | % | 150 |
Insulation Resistance Constant at 20°C | Min | GΩ.m | 40 |
Insulation Resistance Constant at 90°C | Min | GΩ.m | 0.002 |
Sheath | |||
Test Parameter | Unit | Specified Value | |
Nominal Overall Dimension | Height | mm | 5.4 |
Width | 12.1 | ||
Nominal Thickness | mm | 1.0 | |
Minimum Thickness | mm | 0.75 | |
Tensile Strength (Before Ageing) | Min | N/mm2 | 6.0 |
Elongation (Before Ageing) | Min | % | 150 |
General | |||
Test Parameter | Unit | Specified Value | |
High Voltage test – (3.5kV a.c) | – | No Break Down | |
Minimum Installation Bending Radius – During Installation | mm | 53 | |
Minimum Installation Bending Radius – Installed | mm | 53 |